@article{oai:toyama.repo.nii.ac.jp:00004493, author = {堀田, 剛 and 春田, 清 and 大谷, 博信 and 北村, 岩雄 and 藤田, 宏 and 池田, 長康}, journal = {富山大学工学部紀要}, month = {Feb}, note = {There is ground fault as one of the most impotant problems in distribution lines. It is urgently necessary to establish the technology to distinguish the causes of their faults for preventing them beforehand or finding their locations at the early stages. The current signals caused by one line grounding fault in the distribution lines consisting of the neutral system with grounding reactors were simulated by PSPICE program. It is found from the simulations that the first peak of the fault current signal depends on both the grounding resistance and the capacitance to ground, the compensation effect due to reactors comes out to the steady state current after the fault and the amplitude of the current is larger as the grounding resistance is smaller., 配電線における重要な問題の一つとして地絡事故がある。これらの事故を未然に防ぐか,または早期の段階でその位置を見付けるため,事故の原因を明らかにする技術を確立することは緊急に必要なことである。分散リアクトル接地系配電線における一線地絡事故の電流信号をPSPICEプログラムによってシミュレーションした。このシミュレーションから,一線地絡事故の電流信号の第1ピークは接地抵抗と対地静電容量に依存し,リアクトルの補償効果は事故後の定常電流に現れ,その電流の大きさは接地抵抗が小さい程,大きいということが分かった。, Article, 富山大学工学部紀要,46, Page 25-30}, pages = {25--30}, title = {分散リアクトル接地系配電線における1線地絡電流に関する基礎研究}, volume = {46}, year = {1995} }