@article{oai:toyama.repo.nii.ac.jp:00004052, author = {上野, 亨 and 藤田, 宏 and 前田, 勉}, journal = {富山大学工学部紀要}, month = {Mar}, note = {It has been found out that the neon transformer sometimes overheats,when it is shortcircuited and the discharge occurs in air between the secondary lines. This paper reports the experiments that have been carried out to reserch the causes of this overheat accident. As the results of these experiments,interesting phenomena were found. That is,the primary and the secondary current(rms) increases abnormally when the wind blows through the discharging air gap,and it follows from this that the temperature of winding also rises abnormally. we are convinced this report offers some useful data to the protection and the designing of the neon transformer., ネオン照明などに使用されているネオン変圧器が二次回路の断線事故,その他の負荷の損傷により大気中で放電を生じている場合に,このネオン変圧器が焼損するという報告をうけた。 われわれはこの事故の原因を究明するため実験を行なったところ,放電電極間に微風があたると一次および二次電流(rms)が異常に増加し,さらに,巻線温度が二次回路短絡のときよりもかなり高くなるという現象を確認したので報告する。, Article, 富山大学工学部紀要,21}, pages = {37--40}, title = {ネオン変圧器の異常現象について}, volume = {21}, year = {1970} }