WEKO3
アイテム
{"_buckets": {"deposit": "40622f98-a6f2-417c-8314-7058478c1435"}, "_deposit": {"created_by": 3, "id": "4062", "owners": [3], "pid": {"revision_id": 0, "type": "depid", "value": "4062"}, "status": "published"}, "_oai": {"id": "oai:toyama.repo.nii.ac.jp:00004062", "sets": ["581"]}, "author_link": ["11213"], "item_3_alternative_title_19": {"attribute_name": "その他(別言語等)のタイトル", "attribute_value_mlt": [{"subitem_alternative_title": "Fundamental Study of Froth Contact coolers"}]}, "item_3_biblio_info_7": {"attribute_name": "書誌情報", "attribute_value_mlt": [{"bibliographicIssueDates": {"bibliographicIssueDate": "1970-03", "bibliographicIssueDateType": "Issued"}, "bibliographicPageEnd": "102", "bibliographicPageStart": "99", "bibliographicVolumeNumber": "21", "bibliographic_titles": [{"bibliographic_title": "富山大学工学部紀要"}]}]}, "item_3_description_15": {"attribute_name": "フォーマット", "attribute_value_mlt": [{"subitem_description": "application/pdf", "subitem_description_type": "Other"}]}, "item_3_description_4": {"attribute_name": "抄録", "attribute_value_mlt": [{"subitem_description": "The froth contact cooler is a kind of evaporative cooler, which is one of the apparatuses to meet the shortage of cooling water. Functionally the froth contact cooler is an application of bubble columns to a coolelr, that is, its tube-bundle is dipped froth layer of coooling water. This study is to obtain the data to be used in designing froth contact cooler, using heater instead of tube-bundle, and the heat transfer coefficient between froth layer and wall of heater, and mass transfer coefficient between air and froth layer were obtained experimentally and cqrrelated; and furthermore compared with the other paper.", "subitem_description_type": "Abstract"}, {"subitem_description": "泡沫接触式冷却器は気泡塔を冷却器として適用したものであり,蒸発冷却器の一種である。\nすなわち気泡の中に水が蒸発し,そのときの潜熱と空気への顕熱の移動により被冷却流体(プロセス流体)を冷却するものである。\n気泡塔に関する既往の文献によると気泡と接触する壁側の伝熱係数は気泡のない静止液と外壁との伝熱係数にくらべて6~10倍に増加することがわかっている。\n従来から多くの冷却水を使用する水冷式の冷却器が使用されているが,最近の用水事情の悪化からその対策として本冷却器が考えられたもので,使用水の量は若干の飛沫同伴と蒸発水量だけである。\n多孔板を通して液中に気泡が形成される気泡塔内の伝熱に関する研究については,Fairら,Kölbelらおよび吉留らの報告があるが,それらはいずれも空気流量の小さいところについて検討をおこなっている。\n筆者はそれらと比較しながら冷却器に適するような空気流量の大きい,いわゆる気泡の撹乱した状態(泡沫層という)の範囲を実験的に測定した。", "subitem_description_type": "Abstract"}]}, "item_3_description_40": {"attribute_name": "資源タイプ(DSpace)", "attribute_value_mlt": [{"subitem_description": "Article", "subitem_description_type": "Other"}]}, "item_3_description_6": {"attribute_name": "引用", "attribute_value_mlt": [{"subitem_description": "富山大学工学部紀要,21, 99-102.(1970)", "subitem_description_type": "Other"}]}, "item_3_full_name_3": {"attribute_name": "著者別名", "attribute_value_mlt": [{"nameIdentifiers": [{"nameIdentifier": "11213", "nameIdentifierScheme": "WEKO"}, {"nameIdentifier": "1000080019166", "nameIdentifierScheme": "CiNii ID", "nameIdentifierURI": "http://ci.nii.ac.jp/nrid/1000080019166"}, {"nameIdentifier": "80019166", "nameIdentifierScheme": "e-Rad", "nameIdentifierURI": "https://nrid.nii.ac.jp/nrid/1000080019166"}], "names": [{"name": "Miyashita, Hisashi"}]}]}, "item_3_identifier_registration": {"attribute_name": "ID登録", "attribute_value_mlt": [{"subitem_identifier_reg_text": "10.15099/00004056", "subitem_identifier_reg_type": "JaLC"}]}, "item_3_publisher_33": {"attribute_name": "出版者", "attribute_value_mlt": [{"subitem_publisher": "富山大学工学部"}]}, "item_3_source_id_10": {"attribute_name": "書誌レコードID", "attribute_value_mlt": [{"subitem_source_identifier": "AN00175872", "subitem_source_identifier_type": "NCID"}]}, "item_3_source_id_8": {"attribute_name": "ISSN", "attribute_value_mlt": [{"subitem_source_identifier": "03871339", "subitem_source_identifier_type": "ISSN"}]}, "item_3_subject_22": {"attribute_name": "国立国会図書館分類", "attribute_value_mlt": [{"subitem_subject": "ZM2", "subitem_subject_scheme": "NDLC"}]}, "item_3_version_type_16": {"attribute_name": "著者版フラグ", "attribute_value_mlt": [{"subitem_version_resource": "http://purl.org/coar/version/c_970fb48d4fbd8a85", "subitem_version_type": "VoR"}]}, "item_creator": {"attribute_name": "著者", "attribute_type": "creator", "attribute_value_mlt": [{"creatorNames": [{"creatorName": "宮下, 尚"}], "nameIdentifiers": [{"nameIdentifier": "11213", "nameIdentifierScheme": "WEKO"}, {"nameIdentifier": "1000080019166", "nameIdentifierScheme": "CiNii ID", "nameIdentifierURI": "http://ci.nii.ac.jp/nrid/1000080019166"}, {"nameIdentifier": "80019166", "nameIdentifierScheme": "e-Rad", "nameIdentifierURI": "https://nrid.nii.ac.jp/nrid/1000080019166"}]}]}, "item_files": {"attribute_name": "ファイル情報", "attribute_type": "file", "attribute_value_mlt": [{"accessrole": "open_date", "date": [{"dateType": "Available", "dateValue": "2016-02-16"}], "displaytype": "detail", "download_preview_message": "", "file_order": 0, "filename": "Kokiyo_21_01_Page099to102.pdf", "filesize": [{"value": "6.7 MB"}], "format": "application/pdf", "future_date_message": "", "is_thumbnail": false, "licensetype": "license_free", "mimetype": "application/pdf", "size": 6700000.0, "url": {"label": "Kokiyo_21_01_Page099to102.pdf", "url": "https://toyama.repo.nii.ac.jp/record/4062/files/Kokiyo_21_01_Page099to102.pdf"}, "version_id": "280abef2-3d53-4e5a-9597-102d8152b5bf"}]}, "item_keyword": {"attribute_name": "キーワード", "attribute_value_mlt": [{"subitem_subject": "泡沫接触式冷却器", "subitem_subject_scheme": "Other"}, {"subitem_subject": "蒸発冷却器", "subitem_subject_scheme": "Other"}, {"subitem_subject": "被冷却流体", "subitem_subject_scheme": "Other"}, {"subitem_subject": "プロセス流体", "subitem_subject_scheme": "Other"}]}, "item_language": {"attribute_name": "言語", "attribute_value_mlt": [{"subitem_language": "jpn"}]}, "item_resource_type": {"attribute_name": "資源タイプ", "attribute_value_mlt": [{"resourcetype": "departmental bulletin paper", "resourceuri": "http://purl.org/coar/resource_type/c_6501"}]}, "item_title": "泡沫接触式冷却器の基礎研究", "item_titles": {"attribute_name": "タイトル", "attribute_value_mlt": [{"subitem_title": "泡沫接触式冷却器の基礎研究"}]}, "item_type_id": "3", "owner": "3", "path": ["581"], "permalink_uri": "https://doi.org/10.15099/00004056", "pubdate": {"attribute_name": "公開日", "attribute_value": "2012-09-26"}, "publish_date": "2012-09-26", "publish_status": "0", "recid": "4062", "relation": {}, "relation_version_is_last": true, "title": ["泡沫接触式冷却器の基礎研究"], "weko_shared_id": 3}
泡沫接触式冷却器の基礎研究
https://doi.org/10.15099/00004056
https://doi.org/10.15099/00004056e52c1439-c9e3-4774-8d8f-6d36240d1eb7
名前 / ファイル | ライセンス | アクション |
---|---|---|
Kokiyo_21_01_Page099to102.pdf (6.7 MB)
|
|
Item type | 紀要論文 / Departmental Bulletin Paper(1) | |||||
---|---|---|---|---|---|---|
公開日 | 2012-09-26 | |||||
タイトル | ||||||
タイトル | 泡沫接触式冷却器の基礎研究 | |||||
言語 | ||||||
言語 | jpn | |||||
キーワード | ||||||
主題Scheme | Other | |||||
主題 | 泡沫接触式冷却器 | |||||
キーワード | ||||||
主題Scheme | Other | |||||
主題 | 蒸発冷却器 | |||||
キーワード | ||||||
主題Scheme | Other | |||||
主題 | 被冷却流体 | |||||
キーワード | ||||||
主題Scheme | Other | |||||
主題 | プロセス流体 | |||||
資源タイプ | ||||||
資源タイプ識別子 | http://purl.org/coar/resource_type/c_6501 | |||||
資源タイプ | departmental bulletin paper | |||||
ID登録 | ||||||
ID登録 | 10.15099/00004056 | |||||
ID登録タイプ | JaLC | |||||
著者 |
宮下, 尚
× 宮下, 尚 |
|||||
著者別名 | ||||||
姓名 | Miyashita, Hisashi | |||||
その他(別言語等)のタイトル | ||||||
その他のタイトル | Fundamental Study of Froth Contact coolers | |||||
抄録 | ||||||
内容記述タイプ | Abstract | |||||
内容記述 | The froth contact cooler is a kind of evaporative cooler, which is one of the apparatuses to meet the shortage of cooling water. Functionally the froth contact cooler is an application of bubble columns to a coolelr, that is, its tube-bundle is dipped froth layer of coooling water. This study is to obtain the data to be used in designing froth contact cooler, using heater instead of tube-bundle, and the heat transfer coefficient between froth layer and wall of heater, and mass transfer coefficient between air and froth layer were obtained experimentally and cqrrelated; and furthermore compared with the other paper. | |||||
抄録 | ||||||
内容記述タイプ | Abstract | |||||
内容記述 | 泡沫接触式冷却器は気泡塔を冷却器として適用したものであり,蒸発冷却器の一種である。 すなわち気泡の中に水が蒸発し,そのときの潜熱と空気への顕熱の移動により被冷却流体(プロセス流体)を冷却するものである。 気泡塔に関する既往の文献によると気泡と接触する壁側の伝熱係数は気泡のない静止液と外壁との伝熱係数にくらべて6~10倍に増加することがわかっている。 従来から多くの冷却水を使用する水冷式の冷却器が使用されているが,最近の用水事情の悪化からその対策として本冷却器が考えられたもので,使用水の量は若干の飛沫同伴と蒸発水量だけである。 多孔板を通して液中に気泡が形成される気泡塔内の伝熱に関する研究については,Fairら,Kölbelらおよび吉留らの報告があるが,それらはいずれも空気流量の小さいところについて検討をおこなっている。 筆者はそれらと比較しながら冷却器に適するような空気流量の大きい,いわゆる気泡の撹乱した状態(泡沫層という)の範囲を実験的に測定した。 |
|||||
引用 | ||||||
内容記述タイプ | Other | |||||
内容記述 | 富山大学工学部紀要,21, 99-102.(1970) | |||||
書誌情報 |
富山大学工学部紀要 巻 21, p. 99-102, 発行日 1970-03 |
|||||
ISSN | ||||||
収録物識別子タイプ | ISSN | |||||
収録物識別子 | 03871339 | |||||
書誌レコードID | ||||||
収録物識別子タイプ | NCID | |||||
収録物識別子 | AN00175872 | |||||
フォーマット | ||||||
内容記述タイプ | Other | |||||
内容記述 | application/pdf | |||||
著者版フラグ | ||||||
出版タイプ | VoR | |||||
出版タイプResource | http://purl.org/coar/version/c_970fb48d4fbd8a85 | |||||
国立国会図書館分類 | ||||||
主題Scheme | NDLC | |||||
主題 | ZM2 | |||||
出版者 | ||||||
出版者 | 富山大学工学部 | |||||
資源タイプ(DSpace) | ||||||
内容記述タイプ | Other | |||||
内容記述 | Article |